§192.373. Service lines: Cast iron and ductile iron.

49 C.F.R. § 192.373

(a)
Cast or ductile iron pipe less than 6 inches (152 millimeters) in diameter may not be installed for service lines.
(b)
If cast iron pipe or ductile iron pipe is installed for use as a service line, the part of the service line which extends through the building wall must be of steel pipe.
(c)
A cast iron or ductile iron service line may not be installed in unstable soil or under a building.