§112.55-15. Capacity of storage batteries.

46 C.F.R. § 112.55-15

(a)
A storage battery for an emergency lighting and power system must have the capacity—
(1)
To close all watertight doors two times;
(2)
To open all watertight doors once; and
(3)
To carry the remaining emergency loads continuously for the time prescribed in § 112.05-5(a), table 112.05-5(a).
(b)
At the end of the time specified in paragraph (a) of this section, the potential of the storage battery must be at least 88 percent of the standard voltage.