US Codex
C.F.R.
Browse by date
Notes

§112.55-10. Storage battery charging.

46 C.F.R. § 112.55-10

(a)
Each storage battery installation for emergency lighting and power, and starting batteries for an emergency diesel or gas turbine driven generator set, must have apparatus to automatically maintain the battery fully charged.
(b)
When the ship's service generating plant is available, the battery must have a continuous trickle charge, except that after discharge the battery must be charged automatically at a higher rate.
(c)
Charging operations must not cause an absence of battery power.
(d)
There must be instruments to show the rate of charge.
Notes, amendments, and revision history

Authority

Authority: 46 U.S.C. 3306, 3703; DHS Delegation No. 00170.1, Revision No. 01.2.

Source

Source: CGD 74-125A, 47 FR 15267, Apr. 8, 1982, unless otherwise noted.