US Codex
C.F.R.
Browse by date
Notes

§280.40. General requirements for all UST systems. — Inbound Citations

40 C.F.R. § 280.40

Cited by 2 regulations in release Current.

Citations to §280.40(a)(3)

  • (a) Methods which alert the operator to the presence of a leak by restricting or shutting off the flow of regulated substances through piping or triggering an audible or visual alarm may be used only if they detect leaks of 3 gallons per hour at 10 pounds per square inch line pressure within 1 hour. An annual test of the operation of the leak detector must be conducted in accordance with § 280.40(a)(3).
  • (1) The results of annual operation tests conducted in accordance with § 280.40(a)(3) must be maintained for three years. At a minimum, the results must list each component tested, indicate whether each component tested meets criteria in § 280.40(a)(3) or needs to have action taken, and describe any action taken to correct an issue; and