§149.665. What are the requirements for a general alarm system?

33 C.F.R. § 149.665

Each pumping platform complex must have a general alarm system that:
(a)
Is capable of being manually activated by using alarm boxes;
(b)
Is audible in all parts of the pumping platform complex, except in areas of high ambient noise levels where hearing protection is required under § 150.613 of this chapter; and
(c)
Has a high intensity flashing light in areas where hearing protection is used.