§127.103. Piers and wharves.

33 C.F.R. § 127.103

(a)
If the waterfront facility handling LNG is in a region subject to earthquakes, the piers and wharves must be designed to resist earthquake forces.
(b)
Substructures, except moorings and breasting dolphins, that support or are within 5 meters (16.4 feet) of any pipe or equipment containing LNG, or are within 15 meters (49.2 feet) of a loading flange, must—
(1)
Be made of concrete or steel; and
(2)
Have a fire endurance rating of not less than two hours.
(c)
LNG or LPG storage tanks must have the minimum volume necessary for—
(1)
Surge protection;
(2)
Pump suction supply; or
(3)
Other process needs.