49 C.F.R. §§ 236.201–236.203

3 sections in range

§236.201. Track-circuit control of signals.

49 C.F.R. § 236.201

The control circuits for home signal aspects with indications more favorable than “proceed at restricted speed” shall be controlled automatically by track circuits extending through the entire block.
Notes, amendments, and revision history

Authority

Authority: 49 U.S.C. 20102-20103, 20107, 20133, 20141, 20157, 20301-20303, 20306, 20501-20505, 20701-20703, 21301-21302, 21304; 28 U.S.C. 2461 note; and 49 CFR 1.89.

Source

Source: 33 FR 19684, Dec. 25, 1968, unless otherwise noted.

§236.202. Signal governing movements over hand-operated switch.

49 C.F.R. § 236.202

Signal governing movements over hand-operated switch in the facing direction shall display its most restrictive aspect when the points are open one-fourth inch or more and, in the trailing direction, three-eighths inch or more, except that where a separate aspect is displayed for facing movements over the switch in the normal and in the reverse position, the signal shall display its most restrictive aspect when the switch points are open one-fourth inch or more from either the normal or reverse position.
Notes, amendments, and revision history

Authority

Authority: 49 U.S.C. 20102-20103, 20107, 20133, 20141, 20157, 20301-20303, 20306, 20501-20505, 20701-20703, 21301-21302, 21304; 28 U.S.C. 2461 note; and 49 CFR 1.89.

Source

Source: 33 FR 19684, Dec. 25, 1968, unless otherwise noted.

§236.203. Hand operated crossover between main tracks; protection.

49 C.F.R. § 236.203

At hand-operated crossover between main tracks, protection shall be provided by one of the following:
(a)
An arrangement of one or more track circuits and switch circuit controllers,
(b)
Facing point locks on both switches of the crossover, with both locks operated by a single lever, or
(c)
Electric locking of the switches of the crossover. Signals governing movements over either switch shall display their most restrictive aspect when any of the following conditions exist:
(1)
Where protection is provided by one or more track circuits and switch circuit controllers, and either switch is open or the crossover is occupied by a train, locomotive or car in such a manner as to foul the main track. It shall not be a violation of this requirement where the presence of sand, rust, dirt, grease or other foreign matter on the rail prevents effective shunting;
(2)
Where facing point locks with a single lever are provided, and either switch is unlocked;
(3)
Where the switches are electrically locked, before the electric locking releases.
Notes, amendments, and revision history

Authority

Authority: 49 U.S.C. 20102-20103, 20107, 20133, 20141, 20157, 20301-20303, 20306, 20501-20505, 20701-20703, 21301-21302, 21304; 28 U.S.C. 2461 note; and 49 CFR 1.89.

Source

Source: 33 FR 19684, Dec. 25, 1968, unless otherwise noted.