§193.2627. Atmospheric corrosion control.

49 C.F.R. § 193.2627

Each exposed component that is subject to atmospheric corrosive attack must be protected from atmospheric corrosion by—
(a)
Material that has been designed and selected to resist the corrosive atmosphere involved; or
(b)
Suitable coating or jacketing.
Notes, amendments, and revision history

Source

Source: Amdt. 193-2, 45 FR 70407, Oct. 23, 1980, unless otherwise noted.

Authority

Authority: 49 U.S.C. 5103, 60102, 60103, 60104, 60108, 60109, 60110, 60113, 60118; and 49 CFR 1.53.

Source

Source: 45 FR 9203, Feb. 11, 1980, unless otherwise noted.

§193.2629. External corrosion control: buried or submerged components.

49 C.F.R. § 193.2629

(a)
Each buried or submerged component that is subject to external corrosive attack must be protected from external corrosion by—
(1)
Material that has been designed and selected to resist the corrosive environment involved; or
(2)
The following means—
(i)
An external protective coating designed and installed to prevent corrosion attack and to meet the requirements of § 192.461 of this chapter; and
(ii)
A cathodic protection system designed to protect components in their entirety in accordance with the requirements of § 192.463 of this chapter and placed in operation before October 23, 1981, or within 1 year after the component is constructed or installed, whichever is later.
(b)
Where cathodic protection is applied, components that are electrically interconnected must be protected as a unit.
Notes, amendments, and revision history

Amendments

[Amdt. 193-2, 45 FR 70407, Oct. 23, 1980, as amended at 47 FR 32720, July 29, 1982]

Source

Source: Amdt. 193-2, 45 FR 70407, Oct. 23, 1980, unless otherwise noted.

Authority

Authority: 49 U.S.C. 5103, 60102, 60103, 60104, 60108, 60109, 60110, 60113, 60118; and 49 CFR 1.53.

Source

Source: 45 FR 9203, Feb. 11, 1980, unless otherwise noted.

Amendments

[Amdt. 193-2, 45 FR 70407, Oct. 23, 1980, as amended at 47 FR 32720, July 29, 1982]

§193.2631. Internal corrosion control.

49 C.F.R. § 193.2631

Each component that is subject to internal corrosive attack must be protected from internal corrosion by—
(a)
Material that has been designed and selected to resist the corrosive fluid involved; or
(b)
Suitable coating, inhibitor, or other means.
Notes, amendments, and revision history

Source

Source: Amdt. 193-2, 45 FR 70407, Oct. 23, 1980, unless otherwise noted.

Authority

Authority: 49 U.S.C. 5103, 60102, 60103, 60104, 60108, 60109, 60110, 60113, 60118; and 49 CFR 1.53.

Source

Source: 45 FR 9203, Feb. 11, 1980, unless otherwise noted.

§193.2633. Interference currents.

49 C.F.R. § 193.2633

(a)
Each component that is subject to electrical current interference must be protected by a continuing program to minimize the detrimental effects of currents.
(b)
Each cathodic protection system must be designed and installed so as to minimize any adverse effects it might cause to adjacent metal components.
(c)
Each impressed current power source must be installed and maintained to prevent adverse interference with communications and control systems.
Notes, amendments, and revision history

Source

Source: Amdt. 193-2, 45 FR 70407, Oct. 23, 1980, unless otherwise noted.

Authority

Authority: 49 U.S.C. 5103, 60102, 60103, 60104, 60108, 60109, 60110, 60113, 60118; and 49 CFR 1.53.

Source

Source: 45 FR 9203, Feb. 11, 1980, unless otherwise noted.

§193.2635. Monitoring corrosion control.

49 C.F.R. § 193.2635

Corrosion protection provided as required by this subpart must be periodically monitored to give early recognition of ineffective corrosion protection, including the following, as applicable:
(a)
Each buried or submerged component under cathodic protection must be tested at least once each calendar year, but with intervals not exceeding 15 months, to determine whether the cathodic protection meets the requirements of § 192.463 of this chapter.
(b)
Each cathodic protection rectifier or other impressed current power source must be inspected at least 6 times each calendar year, but with intervals not exceeding 2 1/2 months, to ensure that it is operating properly.
(c)
Each reverse current switch, each diode, and each interference bond whose failure would jeopardize component protection must be electrically checked for proper performance at least 6 times each calendar year, but with intervals not exceeding 2 1/2 months. Each other interference bond must be checked at least once each calendar year, but with intervals not exceeding 15 months.
(d)
Each component that is protected from atmospheric corrosion must be inspected at intervals not exceeding 3 years.
(e)
If a component is protected from internal corrosion, monitoring devices designed to detect internal corrosion, such as coupons or probes, must be located where corrosion is most likely to occur. However, monitoring is not required for corrosion resistant materials if the operator can demonstrate that the component will not be adversely affected by internal corrosion during its service life. Internal corrosion control monitoring devices must be checked at least two times each calendar year, but with intervals not exceeding 7 1/2 months.
Notes, amendments, and revision history

Source

Source: Amdt. 193-2, 45 FR 70407, Oct. 23, 1980, unless otherwise noted.

Authority

Authority: 49 U.S.C. 5103, 60102, 60103, 60104, 60108, 60109, 60110, 60113, 60118; and 49 CFR 1.53.

Source

Source: 45 FR 9203, Feb. 11, 1980, unless otherwise noted.