§193.2519. Communication systems.
49 C.F.R. § 193.2519
Each LNG plant must have a primary communication system that provides for verbal communications between all operating personnel at their work stations in the LNG plant.
Each LNG plant in excess of 70,000 gallons (265,000 liters) storage capacity must have an emergency communication system that provides for verbal communications between all persons and locations necessary for the orderly shutdown of operating equipment and the operation of safety equipment in time of emergency. The emergency communication system must be independent of and physically separated from the primary communication system and the security communication system under § 193.2909.
Each communication system required by this part must have an auxiliary source of power, except sound-powered equipment.
Notes, amendments, and revision history
Amendments
[45 FR 9203, Feb. 11, 1980, as amended by Amdt. 193-16, 63 FR 37505, July 13, 1998]
Source
Source: Amdt. 193-2, 45 FR 70405, Oct. 23, 1980, unless otherwise noted.
Authority
Authority: 49 U.S.C. 5103, 60102, 60103, 60104, 60108, 60109, 60110, 60113, 60118; and 49 CFR 1.53.
Source
Source: 45 FR 9203, Feb. 11, 1980, unless otherwise noted.
Amendments
[45 FR 9203, Feb. 11, 1980, as amended by Amdt. 193-16, 63 FR 37505, July 13, 1998]