§192.740. Pressure regulating, limiting, and overpressure protection—Individual service lines directly connected to regulated gathering or transmission pipelines.
49 C.F.R. § 192.740
This section applies, except as provided in paragraph (c) of this section, to any service line directly connected to a transmission pipeline or regulated gathering pipeline as determined in § 192.8 that is not operated as part of a distribution system.
Each pressure regulating or limiting device, relief device (except rupture discs), automatic shutoff device, and associated equipment must be inspected and tested at least once every 3 calendar years, not exceeding 39 months, to determine that it is:
In good mechanical condition;
Adequate from the standpoint of capacity and reliability of operation for the service in which it is employed;
Set to control or relieve at the correct pressure consistent with the pressure limits of § 192.197; and to limit the pressure on the inlet of the service regulator to 60 psi (414 kPa) gauge or less in case the upstream regulator fails to function properly; and
Properly installed and protected from dirt, liquids, or other conditions that might prevent proper operation.
This section does not apply to equipment installed on—
A service line that only serves engines that power irrigation pumps;
A service line included in a distribution integrity management plan meeting the requirements of subpart P of this part; or
A service line directly connected to either a production or gathering pipeline other than a regulated gathering line as determined in § 192.8 of this part.
Notes, amendments, and revision history
Amendments
[Amdt. 192-123, 82 FR 7998, Jan. 23, 2017, as amended at 86 FR 2241, Jan. 11, 2021]
Authority
Authority: 30 U.S.C. 185(w)(3), 49 U.S.C. 5103, 60101 et. seq., and 49 CFR 1.97.
Source
Source: 35 FR 13257, Aug. 19, 1970, unless otherwise noted.
Amendments
[Amdt. 192-123, 82 FR 7998, Jan. 23, 2017, as amended at 86 FR 2241, Jan. 11, 2021]