§192.381. Service lines: Excess flow valve performance standards. — Inbound Citations
49 C.F.R. § 192.381
Statutory Authority
Cited by 1 regulation in release Current.
Citations to 49 C.F.R. § 192.381 as a whole
-
(b) An EFV installation must comply with the performance standards in § 192.381. After April 14, 2017, each operator must install an EFV on any new or replaced service line serving the following types of services before the line is activated:(1) A single service line to one SFR;(2) A branched service line to a SFR installed concurrently with the primary SFR service line (i.e., a single EFV may be installed to protect both service lines);(3) A branched service line to a SFR installed off a previously installed SFR service line that does not contain an EFV;(4) Multifamily residences with known customer loads not exceeding 1,000 SCFH per service, at time of service installation based on installed meter capacity, and(5) A single, small commercial customer served by a single service line with a known customer load not exceeding 1,000 SCFH, at the time of meter installation, based on installed meter capacity.