§192.365. Service lines: Location of valves.
49 C.F.R. § 192.365
Relation to regulator or meter. Each service-line valve must be installed upstream of the regulator or, if there is no regulator, upstream of the meter.
Outside valves. Each service line must have a shut-off valve in a readily accessible location that, if feasible, is outside of the building.
Underground valves. Each underground service-line valve must be located in a covered durable curb box or standpipe that allows ready operation of the valve and is supported independently of the service lines.