§98.30-37. Firefighting requirements.
46 C.F.R. § 98.30-37
No person may lift a portable tank on or off a vessel, or transfer a product with a flashpoint of less than 300 °F to or from a portable tank or IBC unless—
Water pressure is maintained on the firemain;
Firehoses, fitted with a Coast Guard-approved combination nozzle, are attached to each fire hydrant in the vicinity of the portable tanks;
Except as provided in § 98.30-39, fire extinguishers of a dry chemical type are—
Located to protect the deck area 10 feet in any horizontal direction from each portable tank and its associated cargo handling system;
Coast Guard approved; and
Capable of covering the deck area without being moved;
In a deck area of 500 square feet or less, there are two or more dry chemical fire extinguishers of 300 pounds or more total capacity of extinguishing agent; and
In a deck area of more than 500 square feet, there are three or more dry chemical fire extinguishers of 450 pounds or more total capacity of extinguishing agent.