§95.16-50. Instructions.
46 C.F.R. § 95.16-50
Simple, complete operating instructions must be conspicuously located at or near any release station and in the extinguishing agent cylinder storage room.
On a system in which extinguishing agent cylinders are stored outside the protected space, operating instructions must also:
Include a schematic diagram of the system; and
Describe alternate methods of discharging the extinguishing agent into protected spaces should the manual releases or stop valve controls fail to operate.