§76.33-10. Location and spacing of accumulators.

46 C.F.R. § 76.33-10

(a)
Smoke accumulators must be located overhead in each compartment. Where liable to physical damage, the accumulators and piping must be suitably protected.
(b)
No spot on the overhead of a protected space may be more than 40 feet from an accumulator.
(c)
Accumulators must not be located closer to the opening of a ventilator than three times the diameter or equivalent diameter of the opening.