§64.77. Inspection and test. — Inbound Citations
46 C.F.R. § 64.77
Statutory Authority
Cited by 3 regulations in release Current.
Citations to §64.77(a)
-
(a) The inspection of the pressure and vacuum relief device required in § 64.77(a) must include—(1) Disassembling;(2) A visual inspection for defective parts; and
Citations to §64.77(b)
-
(a) The 30-month inspection of an MPT required in § 64.77(b) must include—(i) Corrosion;(ii) Cracking of base material; and(iii) Weld defects; and(2) A visual inspection for defective parts and a manual operation of the gauging device, remote operating mechanism, and each valve, except the pressure relief device.
Citations to §64.77(c)
-
(a) The hydrostatic test required in § 64.77(c) includes—(1) Closing each manhole and other openings by normal means of closure;(2) Using wrenches or other tools that are used during normal operations to close the manhole and other openings;(3) Using the same type of gaskets as used in service;(4) If required for the inspection, removing tank insulation;(5) Filling the tank with water and pressurizing to the test pressure indicated on the metal identification plate without leaking; and(6) If fitted with an internal heating coil, the heating coil passing a hydrostatic test at a pressure of 200 psig or more or 50 percent or more above the rated pressure of the coil, whichever is greater.