§62.20-1. Plans for approval.
46 C.F.R. § 62.20-1
The following plans must be submitted to the Coast Guard for approval in accordance with §§ 50.20-5 and 50.20-10 of this chapter:
A general arrangement plan of control and monitoring equipment, control locations, and the systems served.
Control and monitoring console, panel, and enclosure layouts.
Schematic or logic diagrams including functional relationships, a written description of operation, and sequences of events for all modes of operation.
A description of control or monitoring system connections to non-vital systems.
A description of programmable features.
A description of built-in test features and diagnostics.
Design Verification and Periodic Safety test procedures described in subpart 61.40 of this subchapter.
Control system normal and emergency operating instructions.