§181.410. Fixed gas fire extinguishing systems. — Inbound Citations
46 C.F.R. § 181.410
Statutory Authority
Cited by 3 regulations in release Current.
Citations to 46 U.S.C. § 181.410 as a whole
-
(i) Fire detection and extinguishing systems must be installed in compliance with §§ 181.400 through 181.420 of this subchapter.
-
(a) The following spaces must be equipped with a fixed gas fire extinguishing system, in compliance with § 181.410, or other fixed fire extinguishing system specifically approved by the Commandant, except as otherwise allowed by paragraph (b) of this section:(1) A space containing propulsion machinery;(2) A space containing an internal combustion engine of more than 37.3 kW (50 hp);(3) A space containing an oil fired boiler;(4) A space containing machinery powered by gasoline or other fuels having a flash point of 43.3 °C (110 °F) or lower;(5) A space containing a fuel tank for gasoline or any other fuel having a flash point of 43.3 °C (110 °F) or lower;(6) A space containing combustible cargo or ship's stores inaccessible during the voyage (in these types of spaces only carbon dioxide, and not Halon, systems will be allowed);(7) A paint locker; and(8) A storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater).
Citations to §181.410(g)
-
(8) UL 1058-1989, as amended through April 19, 1994, Halogenated Agent Extinguishing System Units (“UL 1058”), IBR approved for § 181.410(g).