§181.310. Fire main and hydrants.
46 C.F.R. § 181.310
A vessel that has a power driven fire pump must have a sufficient number of fire hydrants to reach any part of the vessel using a single length of firehose.
Piping, valves, and fittings in a fire main system must comply with subpart G, part 182, of this chapter.
Each fire hydrant must have a valve installed to allow the firehose to be removed while the fire main is under pressure.
Spanner wrenches must be provided where a 40 millimeter (1.5 inch) diameter firehose is required by § 181.320(b). Existing vessels as of July 22, 2016 have 180 days to comply with this requirement.