§161.002-6. Testing requirements.

46 C.F.R. § 161.002-6

(a)
Devices must be tested and listed for fire service by an accepted independent laboratory, as accepted in accordance with § 159.010 of this subchapter, or by a NRTL as set forth in 29 CFR 1910.7.
(b)
Each fire detection device must comply with the following standards (incorporated by reference, see § 161.002-1) as appropriate:
(1)
Control units— UL 864;
(2)
Heat detectors— UL 521;
(3)
Smoke detectors— UL 268;
(4)
Flame detectors— ANSI/FM 3260;
(5)
Audible alarms— UL 464 or UL 1480;
(6)
Visual alarms— UL 1971; and
(7)
Manual Signaling Boxes— UL 38.
(c)
All devices must be tested by an accepted independent laboratory, as defined in § 159.010 of this subchapter, to meet the marine environment testing requirements in Table 161.002-6(c) of this section. The test parameters are found in IEC 60092-504 (incorporated by reference, see § 161.002-1).
(d)
All fire detection system control units and remote annunciators must have enclosure protection as outlined in part 5 of IEC 60092-504 (incorporated by reference, see § 161.002-1) if the requirements exceed those of 46 CFR 111.01-9. Otherwise, 46 CFR 111.01-9 must be complied with.