§154.703. Methane (LNG).
46 C.F.R. § 154.703
Unless a cargo tank carrying methane (LNG) can withstand the pressure build up due to boil-off for 21 days, the pressure in the cargo tank must be maintained below the set pressure of the safety relief valve for at least 21 days by:
A refrigeration system that meets § 154.702;
A waste heat or catalytic furnace that burns boil-off gas, and—
Maintains the stack exhaust temperature below 535 °C (995 °F);
Exhibits no visible flame; and
Is specially approved by the Commandant (CG-OES);
Boilers, inert gas generators, and combustion engines in the main propelling machinery space that use boil-off gas as fuel; or
Equipment for services, other than those under paragraph (c) of this section, that use boil-off gas as fuel and that are located:
In the main propelling machinery space; or
a space specially approved by the Commandant (CG-OES).