§154.1160. Monitor coverage of system.
46 C.F.R. § 154.1160
The coverage of each dry chemical system monitor under § 154.1150 must not exceed:
10 m (32.8 ft.) at 10 kg/sec (22 lb/sec);
30 m (98.4 ft.) at 25 kg/sec (55 lb/sec);
40 m (131.2 ft.) at 45 kg/sec (99 lb/sec);
An interpolation between 10 m (32.8 ft.) at 10 kg/sec (22 lb/sec) and 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec); or
An interpolation between 30 m (98.4 ft.) at 25 kg/sec (55 lb/sec) and 40 m (131.2 ft.) at 45 kg/sec (99 lb/sec).