§153.284. Characteristics of required quick closing valves.

46 C.F.R. § 153.284

A remotely actuated quick closing shutoff valve required by § 153.530(n) must:
(a)
Be a positive shutoff valve;
(b)
Be of the fail-closed type that closes on loss of power;
(c)
Be capable of local manual closing;
(d)
Close from the time of actuation in 30 seconds or less; and
(e)
Be equipped with a fusible element that melts at less than 104 °C (approx. 220 °F) and closes the valve.