§143.230. Alarms and monitoring.

46 C.F.R. § 143.230

(a)
Each towing vessel must have a reliable means to provide notification when an emergency condition exists or an essential system develops problems that require attention. The following alarms must be provided:
(1)
Main engine low lubricating oil pressure;
(2)
Main engine high cooling water temperature;
(3)
Auxiliary generator engine low lubricating oil pressure;
(4)
Auxiliary generator engine high cooling water temperature;
(5)
High bilge levels;
(6)
Low hydraulic steering fluid levels, if applicable; and
(7)
Low fuel level, if fitted with a day tank.
(b)
Alarms must—
(1)
Be visible and audible at each operating station. The alarm located at the operating station may be a summary alarm; if the alarm at the operating station is a summary alarm, the specific alarm condition must be indicated at the machinery or bilge location;
(2)
Have a means to test actuation at each operating station or have a continuous self-monitoring alarm system which actuates if an alarm point fails or becomes disabled;
(3)
Continue until they are acknowledged; and
(4)
Not interfere with night vision at the operating station.
(c)
The following systems must be equipped with gauges at the machinery location:
(1)
Main engine lubricating oil pressure and main engine RPM;
(2)
Main engine cooling water temperature;
(3)
Auxiliary generator engine lubricating oil pressure and auxiliary generator engine RPM;
(4)
Auxiliary generator engine cooling water temperature; and
(5)
Hydraulic steering fluid pressure, if the vessel is equipped with hydraulic steering systems.