§132.310. Fixed fire-extinguishing systems for paint lockers.

46 C.F.R. § 132.310

(a)
Except as provided by paragraph (b) of this section, a fixed gaseous fire-extinguishing system or another approved fixed fire-extinguishing system must be installed in each paint locker.
(b)
No fixed fire-extinguishing system need be installed in a paint locker that is—
(1)
Less than 1.7 cubic meters (60 cubic feet) in volume;
(2)
Accessible only from the weather deck; and
(3)
Not adjacent to a tank for flammable or combustible liquid.
(c)
Each fixed fire-extinguishing system installed must comply with part 95 of this chapter or be approved by the Commanding Officer, Marine Safety Center.
Notes, amendments, and revision history

Authority

Authority: 46 U.S.C. 3306, 3307; sec. 617, Pub. L. 111-281, 124 Stat. 2905; DHS Delegation 00170.1, Revision No. 01.4.