§129.326. Dual-voltage generators.
46 C.F.R. § 129.326
If a dual-voltage generator is installed on an OSV—
The neutral of the dual-voltage system must be solidly grounded at the switchboard's neutral bus and be accessible for checking the insulation resistance of the generator; and
Ground detection must be provided that—
For an alternating-current system, complies with § 111.05-27 of this chapter; and
For a direct-current system, complies with § 111.05-29 of this chapter.