46 C.F.R. § 118.400
(a)
The following spaces must be equipped with a fixed gas fire extinguishing system, in compliance with
§ 118.410 of this part, or other fixed fire extinguishing system specifically approved by the Commandant, except as otherwise allowed by
paragraph (b) of this section:
(1)
A space containing propulsion machinery;
(2)
A space containing an internal combustion engine of more than 50 hp;
(3)
A space containing an oil fired boiler;
(4)
A space containing combustible cargo or ship's stores inaccessible during the voyage (a carbon dioxide system must be installed in such a space, and Halon systems are not allowed);
(6)
A storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater).
(b)
Alternative system types and exceptions to the requirements of paragraph (a) of this section are—
(1)
A fixed gas fire extinguishing system, which is capable of automatic discharge upon heat detection, may only be installed in a normally unoccupied space with a gross volume of not more than 170 cubic meters (6,000 cubic feet);
(2)
A pre-engineered fixed gas extinguishing system must be in compliance with
§ 118.420 of this part and may only be installed in a normally unoccupied machinery space, a paint locker, or a storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater), with a gross volume of not more than 57 cubic meters (2,000 cubic feet);
(3)
A 40-B portable fire extinguisher installed outside the space may be substituted for a fixed gas fire extinguishing system in a storeroom containing flammable liquids (including liquors of 80 proof or higher where liquor is packaged in individual containers of 9.5 liters (2.5 gallons) capacity or greater) or a paint locker, with a volume of not more that 5.7 cubic meters (200 cubic feet);
(4)
A space that is so open to the atmosphere that a fixed gas fire extinguishing system would be ineffective, as determined by the cognizant OCMI, is not required to have a fixed gas fire extinguishing system; and
(5)
Where the amount of carbon dioxide gas required in a fixed fire extinguishing system can be supplied by one portable extinguisher or a semi-portable extinguisher, such an extinguisher may be used subject to the following:
(i)
Cylinders must be installed in a fixed position outside the space protected;
(ii)
The applicator must be installed in a fixed position so as to discharge into the space protected; and
(iii)
Controls must be installed in an accessible location outside the space protected.
Notes, amendments, and revision history
Amendments
[CGD 85-080, 61 FR 917, Jan. 10, 1996, as amended at 62 FR 51351, Sept. 30, 1997; USCG-1999-6216, 64 FR 53227, Oct. 1, 1999; USCG-2012-0196; 81 FR 48270, July 22, 2016]; USCG-2021-0306, 86 FR 73171, Dec. 27, 2021; USCG-2024-1103, 90 FR 52881, Nov. 24, 2025]
Authority
Authority: 46 U.S.C. 2103, 3306; E.O. 12234, 45 FR 58801, 3 CFR, 1980 Comp., p. 277; DHS Delegation 00170.1, Revision No. 01.4.
Source
Source: CGD 85-080, 61 FR 917, Jan. 10, 1996, unless otherwise noted.
Amendments
[CGD 85-080, 61 FR 917, Jan. 10, 1996, as amended at 62 FR 51351, Sept. 30, 1997; USCG-1999-6216, 64 FR 53227, Oct. 1, 1999; USCG-2012-0196; 81 FR 48270, July 22, 2016]; USCG-2021-0306, 86 FR 73171, Dec. 27, 2021; USCG-2024-1103, 90 FR 52881, Nov. 24, 2025]