§113.43-5. Power supply.
46 C.F.R. § 113.43-5
Each steering failure alarm system must be supplied by a circuit that:
Is independent of other steering gear system and steering alarm circuits;
Is fed from the final emergency power source through the emergency distribution panel in the wheelhouse, if installed; and
Has no overcurrent protection except short-circuit protection by an instantaneous fuse or circuit breaker rated or set at 400 to 500 percent of:
The current-carrying capacity of the smallest alarm system interconnecting conductors; or
The normal load of the system.