§113.25-11. Contact makers.
46 C.F.R. § 113.25-11
Each contact maker must—
Have normally open contacts and be constructed in accordance with Type 4 or 4X of NEMA 250 or IP 56 of IEC 60529:2013 (both incorporated by reference; see § 110.10-1 of this subpart) requirements;
Have a switch handle that can be maintained in the “on” position;
Have the “off” and “on” positions of the operating handle permanently marked; and
Have an inductive load rating not less than the connected load or, on large vessels, have auxiliary devices to interrupt the load current.