§112.43-1. Switches.

46 C.F.R. § 112.43-1

An emergency lighting system must not have a switch, except:
(a)
In a distribution panel;
(b)
As required in § 112.43-7; or
(c)
In a circuit that serves a hazardous space such as a paint room or cargo handling room if the switch is located outside of the hazardous location.