§112.05-3. Main-emergency bus-tie.
46 C.F.R. § 112.05-3
Each bus-tie between a main switchboard and an emergency switchboard must:
Disconnect automatically upon loss of potential at the emergency switchboard;
Be arranged to prevent parallel operation of an emergency power source with any other source of electric power, except for interlock systems for momentary transfer of loads; and
If arranged for feedback operation, open automatically upon overload of the emergency power source before the emergency power source is tripped off the line from the overload.