§111.97-9. Overcurrent protection.
46 C.F.R. § 111.97-9
Overcurrent devices must be arranged to isolate a fault with as little disruption of the system as possible. The relationship between the load and the rating or setting of overcurrent devices must meet the following:
The rating or setting of each feeder overcurrent device must be not less than 200 percent of its maximum load.
The rating or setting of a branch circuit overcurrent device must be not more than 25 percent of that of the feeder overcurrent device.