§111.85-1. Electric oil immersion heaters.
46 C.F.R. § 111.85-1
Each oil immersion heater must have the following:
An operating thermostat.
Heating elements that have no electrical contact with the oil.
A high temperature limiting device that—
Opens all conductors to the heater;
Is manually reset; and
Actuates at a temperature below the flashpoint of the oil.
Either—
A low-fluid-level device that opens all conductors to the heater if the operating level drops below the manufacturer's recommended minimum safe level; or
A flow device that opens all conductors to the heater if there is inadequate flow.