§111.51-4. Short-circuit calculations for systems 1500 kilowatts or above.

46 C.F.R. § 111.51-4

Short-circuit calculations must be submitted for systems with an aggregate generating capacity of 1500 kilowatts or more by utilizing one of the following methods:
(a)
Exact calculations using actual impedance and reactance values of system components.
(b)
Estimated calculations using IEC 61363-1— 1998 for AC systems and IEC 61660-1:1997 for DC systems (both incorporated by reference; see § 110.10-1 of this subchapter).
(c)
The estimated calculations using a commercially established analysis procedure for utility or industrial applications.