US Codex
C.F.R.
Browse by date
Notes

§111.30-3. Accessibility of switchboard components and connections.

46 C.F.R. § 111.30-3

Each component and bus bar connection on a switchboard that is not accessible from the rear, except a bus bar connection for a draw-out type circuit breaker, must be within 0.5 m (20 in.) of the front of the switchboard.
Notes, amendments, and revision history

Authority

Authority: 46 U.S.C. 3306, 3703; DHS Delegation No. 00170.1, Revision No. 01.2. Section 111.05-20 and Subpart 111.106 also issued under sec. 617, Pub. L. 111-281, 124 Stat. 2905.

Source

Source: CGD 74-125A, 47 FR 15236, Apr. 8, 1982, unless otherwise noted.