US Codex
C.F.R.
Browse by date
Notes

§111.12-9. Generator cables.

46 C.F.R. § 111.12-9

(a)
The current-carrying capacity of generator cables must not be:
(1)
Less than 115 percent of the continuous generator rating; or
(2)
Less than 115 percent of the overload for a machine with a 2 hour or greater overload rating.
(b)
Generator cables must not be in the bilges.
Notes, amendments, and revision history

Authority

Authority: 46 U.S.C. 3306, 3703; DHS Delegation No. 00170.1, Revision No. 01.2. Section 111.05-20 and Subpart 111.106 also issued under sec. 617, Pub. L. 111-281, 124 Stat. 2905.

Source

Source: CGD 74-125A, 47 FR 15236, Apr. 8, 1982, unless otherwise noted.