US Codex
C.F.R.
Browse by date
Notes

§111.103-7. Ventilation stop stations.

46 C.F.R. § 111.103-7

Each power ventilation system stop station must:
(a)
Be protected by an enclosure with a glass-paneled door on the front;
(b)
Be marked, “In Case of Fire Break Glass and Operate Switch to Stop Ventilation;”
(c)
Have the “stop” position of the switch clearly identified;
(d)
Have a nameplate that identifies the system controlled; and
(e)
Be arranged so that damage to the switch or cable automatically stops the equipment controlled.
Notes, amendments, and revision history

Amendments

[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2020-0075, 88 FR 16365, Mar. 16, 2023]

Authority

Authority: 46 U.S.C. 3306, 3703; DHS Delegation No. 00170.1, Revision No. 01.2. Section 111.05-20 and Subpart 111.106 also issued under sec. 617, Pub. L. 111-281, 124 Stat. 2905.

Source

Source: CGD 74-125A, 47 FR 15236, Apr. 8, 1982, unless otherwise noted.

Amendments

[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2020-0075, 88 FR 16365, Mar. 16, 2023]