§111.103-1. Power ventilation systems except machinery space ventilation systems.
46 C.F.R. § 111.103-1
Each power ventilation system that is not a machinery space ventilation system must have:
A control to stop the ventilation that is—
Outside the space ventilated; and
Grouped with the controls for every power ventilation system to which this section is applicable; and
In addition to the control required by paragraph (a), a stop control that is—
As far as practicable from the control required by paragraph (a) and grouped with the controls for every power ventilation system to which this section is applicable; or
The circuit breakers for ventilation grouped on the main switchboard and marked, “In Case of Fire Trip to Stop Ventilation.”