§111.05-31. Grounding conductors for systems.
46 C.F.R. § 111.05-31
A conductor for grounding a direct-current system must be the larger of:
The largest conductor supplying the system; or
No. 8 AWG (8.4mm 2).
A conductor for grounding the neutral of an alternating-current system must meet Table 111.05-31(b).