§108.175. Contiguous locations.

46 C.F.R. § 108.175

An enclosed space that has direct access to a Division 1 or Division 2 location is the same division as that location, except—
(a)
An enclosed space that has direct access to a Division 1 location is not a hazardous location if—
(1)
The access has self-closing gas-tight doors that form an air lock;
(2)
The ventilation causes greater pressure in the space than in the Division 1 location; and
(3)
Loss of ventilation overpressure activates an alarm at a manned station;
(b)
An enclosed space that has direct access to a Division 1 location can be considered as a Division 2 location if—
(1)
The access has a self-closing, gas-tight door that opens into the space and that has no hold-back device;
(2)
Ventilation causes the air to flow with the door open from the space into the Division 1 location; and
(3)
Loss of ventilation activates an alarm at a manned control station; and
(c)
An enclosed space that has direct access to a Division 2 location is not a hazardous location if—
(1)
The access has a self-closing, gas-tight door that opens into the space and that has no hold-back device;
(2)
Ventilation causes the air to flow with the door open from the space into the Division 2 location; and
(3)
Loss of ventilation activates an alarm at a manned control station.