§108.175. Contiguous locations.
46 C.F.R. § 108.175
An enclosed space that has direct access to a Division 1 or Division 2 location is the same division as that location, except—
An enclosed space that has direct access to a Division 1 location is not a hazardous location if—
The access has self-closing gas-tight doors that form an air lock;
The ventilation causes greater pressure in the space than in the Division 1 location; and
Loss of ventilation overpressure activates an alarm at a manned station;
An enclosed space that has direct access to a Division 1 location can be considered as a Division 2 location if—
The access has a self-closing, gas-tight door that opens into the space and that has no hold-back device;
Ventilation causes the air to flow with the door open from the space into the Division 1 location; and
Loss of ventilation activates an alarm at a manned control station; and
An enclosed space that has direct access to a Division 2 location is not a hazardous location if—
The access has a self-closing, gas-tight door that opens into the space and that has no hold-back device;
Ventilation causes the air to flow with the door open from the space into the Division 2 location; and
Loss of ventilation activates an alarm at a manned control station.
Notes, amendments, and revision history
Authority
Authority: 43 U.S.C. 1333; 46 U.S.C. 3102, 3306; DHS Delegation No. 00170.1, Revision No. 01.4.
Source
Source: CGD 73-251, 43 FR 56808, Dec. 4, 1978, unless otherwise noted.