US Codex
C.F.R.
Browse by date
Notes

§3175.142. Required static tests.

43 C.F.R. § 3175.142

(a)
Instantaneous flow rate. The instantaneous flow rates must meet the criteria in § 3175.141(d) for each test identified in Table 1 to this section, using the gas compositions identified in Table 2 to this section, as prescribed in Table 1 to this section.
(b)
Sums and averages.
(1)
Fixed input values from test 2 in Table 1 to this section must be applied for a period of at least 24 hours.
(2)
At the conclusion of the 24-hour period, the following hourly and daily values must meet the criteria in § 3175.141(d):
(i)
Volume;
(ii)
Integral value;
(iii)
Flow time;
(iv)
Average differential pressure;
(v)
Average static pressure; and
(vi)
Average flowing temperature.
(c)
Other tests. The following additional tests must be performed on the flow-computer software:
(1)
Each parameter of the configuration log must be changed to ensure the event log properly records the changes according to the variables listed in § 3175.104(c); and
(2)
Inputs simulating a 15 percent and 150 percent over-range of the differential and static-pressure transducer's calibrated span must be entered to verify that the over-range condition triggers an alarm or an entry in the event log.
Notes, amendments, and revision history

Source

Source: 81 FR 81609, Nov. 17, 2016, unless otherwise noted.

Authority

Authority: 25 U.S.C. 396d and 2107; 30 U.S.C. 189, 306, 359, and 1751; and 43 U.S.C. 1732(b), 1733, and 1740.

Source

Source: 81 FR 81421, Nov. 17, 2016, unless otherwise noted.