§3175.142. Required static tests.
43 C.F.R. § 3175.142
Instantaneous flow rate. The instantaneous flow rates must meet the criteria in § 3175.141(d) for each test identified in Table 1 to this section, using the gas compositions identified in Table 2 to this section, as prescribed in Table 1 to this section.
Sums and averages.
Fixed input values from test 2 in Table 1 to this section must be applied for a period of at least 24 hours.
At the conclusion of the 24-hour period, the following hourly and daily values must meet the criteria in § 3175.141(d):
Volume;
Integral value;
Flow time;
Average differential pressure;
Average static pressure; and
Average flowing temperature.
Other tests. The following additional tests must be performed on the flow-computer software:
Each parameter of the configuration log must be changed to ensure the event log properly records the changes according to the variables listed in § 3175.104(c); and
Inputs simulating a 15 percent and 150 percent over-range of the differential and static-pressure transducer's calibrated span must be entered to verify that the over-range condition triggers an alarm or an entry in the event log.