§761.326. Conducting the comparison study.
40 C.F.R. § 761.326
Extract or analyze the comparison study samples using the alternative method. For an alternative extraction method or alternative analytical method to be comparable to the methods required in § 761.292, all of the following conditions must be met.
All samples having PCB concentrations greater than or equal to the level of concern, as measured by the methods required in § 761.292, are found to be greater than or equal to the level of concern as measured by the alternative method (no false negatives).
Only one sample which contains PCBs at a level less than the level of concern, as measured by the methods required in § 761.292, is found to have a PCB concentration greater than the level of concern as measured by the alternative method (false positive); and all other samples which contain PCBs at levels less than the level of concern, as measured by the methods required in § 761.292, are found by the alternative method to have PCBs less than the level of concern (there are no additional false positives).
Notes, amendments, and revision history
Source
Source: 63 FR 35468, June 29, 1998, unless otherwise noted.
Authority
Authority: 15 U.S.C. 2605, 2607, 2611, 2614, and 2616 and 42 U.S.C. 6939g.
Source