US Codex
C.F.R.
Browse by date
Notes

§60.82. Standard for sulfur dioxide. — Inbound Citations

40 C.F.R. § 60.82

Cited by 2 regulations in release Current.

Citations to 40 C.F.R. § 60.82 as a whole

  • (e) For the purpose of reports under § 60.7(c), periods of excess emissions shall be all three-hour periods (or the arithmetic average of three consecutive one-hour periods) during which the integrated average sulfur dioxide emissions exceed the applicable standards under § 60.82.
  • (b) The owner or operator shall determine compliance with the SO2 acid mist, and visible emission standards in §§ 60.82 and 60.83 as follows:
    (1) The emission rate (E) of acid mist or SO2 shall be computed for each run using the following equation:
    (2) Method 8 shall be used to determine the acid mist and SO2 concentrations (C's) and the volumetric flow rate (Qsd) of the effluent gas. The moisture content may be considered to be zero. The sampling time and sample volume for each run shall be at least 60 minutes and 1.15 dscm (40.6 dscf).
    (3) Suitable methods shall be used to determine the production rate (P) of 100 percent H2SO4 for each run. Material balance over the production system shall be used to confirm the production rate.
    (4) Method 9 and the procedures in § 60.11 shall be used to determine opacity.