§60.502. Standard for Volatile Organic Compound (VOC) emissions from bulk gasoline terminals. — Inbound Citations

40 C.F.R. § 60.502

Cited by 24 regulations in release Current.

Citations to 40 U.S.C. § 60.502 as a whole

  • (1) Each owner or operator of loading racks at a bulk gasoline terminal subject to the provisions of this subpart shall comply with the requirements in § 60.502 of this chapter except for paragraphs (b), (c), and (j) of that section. For purposes of this section, the term “affected facility” used in § 60.502 means the loading racks that load gasoline cargo tanks at the bulk gasoline terminals subject to the provisions of this subpart.

Citations to §60.502(b)

  • (b) Immediately before the performance test required to determine compliance with § 60.502 (b), (c), and (h), the owner or operator shall use Method 21 to monitor for leakage of vapor all potential sources in the terminal's vapor collection system equipment while a gasoline tank truck is being loaded. The owner or operator shall repair all leaks with readings of 10,000 ppm (as methane) or greater before conducting the performance test.
  • (1) Each owner or operator of loading racks at a bulk gasoline terminal subject to the provisions of this subpart shall comply with the requirements in § 60.502 of this chapter except for paragraphs (b), (c), and (j) of that section. For purposes of this section, the term “affected facility” used in § 60.502 means the loading racks that load gasoline cargo tanks at the bulk gasoline terminals subject to the provisions of this subpart.

Citations to §60.502(c)

  • (b) Immediately before the performance test required to determine compliance with § 60.502 (b), (c), and (h), the owner or operator shall use Method 21 to monitor for leakage of vapor all potential sources in the terminal's vapor collection system equipment while a gasoline tank truck is being loaded. The owner or operator shall repair all leaks with readings of 10,000 ppm (as methane) or greater before conducting the performance test.
  • (1) Each owner or operator of loading racks at a bulk gasoline terminal subject to the provisions of this subpart shall comply with the requirements in § 60.502 of this chapter except for paragraphs (b), (c), and (j) of that section. For purposes of this section, the term “affected facility” used in § 60.502 means the loading racks that load gasoline cargo tanks at the bulk gasoline terminals subject to the provisions of this subpart.

Citations to §60.502(e)

Citations to §60.502(e)(1)

Citations to §60.502(e)(2)

Citations to §60.502(e)(3)

Citations to §60.502(e)(4)

Citations to §60.502(e)(5)

Citations to §60.502(f)

Citations to §60.502(g)

Citations to §60.502(h)

  • (b) Immediately before the performance test required to determine compliance with § 60.502 (b), (c), and (h), the owner or operator shall use Method 21 to monitor for leakage of vapor all potential sources in the terminal's vapor collection system equipment while a gasoline tank truck is being loaded. The owner or operator shall repair all leaks with readings of 10,000 ppm (as methane) or greater before conducting the performance test.
  • (1) Follow the steps in 40 CFR 60.502(e) to ensure that organic liquids are loaded only into vapor-tight transport vehicles and comply with the provisions in 40 CFR 60.502(f) through (i), except substitute the term “transport vehicle” at each occurrence of the term “tank truck” or “gasoline tank truck” in those paragraphs.
  • (e) As an alternative to § 60.502(h) and (i) or § 60.502a(h) and (i) of this chapter as specified in paragraph (a) of this section, the owner or operator may comply with paragraphs (e)(1) and (2) of this section.
    (1) The owner or operator shall design and operate the vapor processing system, vapor collection system, and liquid loading equipment to prevent gauge pressure in the railcar gasoline cargo tank from exceeding the applicable test limits in § 63.425(e) and (i) during product loading. This level is not to be exceeded when measured by the procedures specified in § 60.503(d) of this chapter during any performance test or performance evaluation conducted under § 63.425(b) or (c).
    (2) No pressure-vacuum vent in the bulk' gasoline terminal's vapor processing system or vapor collection system may begin to open at a system pressure less than the applicable test limits in § 63.425(e) or (i).

Citations to §60.502(i)

  • (1) Follow the steps in 40 CFR 60.502(e) to ensure that organic liquids are loaded only into vapor-tight transport vehicles and comply with the provisions in 40 CFR 60.502(f) through (i), except substitute the term “transport vehicle” at each occurrence of the term “tank truck” or “gasoline tank truck” in those paragraphs.
  • (e) As an alternative to § 60.502(h) and (i) or § 60.502a(h) and (i) of this chapter as specified in paragraph (a) of this section, the owner or operator may comply with paragraphs (e)(1) and (2) of this section.
    (1) The owner or operator shall design and operate the vapor processing system, vapor collection system, and liquid loading equipment to prevent gauge pressure in the railcar gasoline cargo tank from exceeding the applicable test limits in § 63.425(e) and (i) during product loading. This level is not to be exceeded when measured by the procedures specified in § 60.503(d) of this chapter during any performance test or performance evaluation conducted under § 63.425(b) or (c).
    (2) No pressure-vacuum vent in the bulk' gasoline terminal's vapor processing system or vapor collection system may begin to open at a system pressure less than the applicable test limits in § 63.425(e) or (i).

Citations to §60.502(j)

  • (c) A record of each monthly leak inspection required under § 60.502(j) shall be kept on file at the terminal for at least 2 years. Inspection records shall include, as a minimum, the following information:
  • (1) Each owner or operator of loading racks at a bulk gasoline terminal subject to the provisions of this subpart shall comply with the requirements in § 60.502 of this chapter except for paragraphs (b), (c), and (j) of that section. For purposes of this section, the term “affected facility” used in § 60.502 means the loading racks that load gasoline cargo tanks at the bulk gasoline terminals subject to the provisions of this subpart.