US Codex
C.F.R.
Browse by date
Notes

§141.860. Violations.

40 C.F.R. § 141.860

(a)
E. coli MCL Violation. A system is in violation of the MCL for E. coli when any of the conditions identified in paragraphs (a)(1) through (a)(4) of this section occur.
(1)
The system has an <I>E. coli-positive repeat sample following a total coliform-positive routine sample.
(2)
The system has a total coliform-positive repeat sample following an <I>E. coli-positive routine sample.
(3)
The system fails to take all required repeat samples following an <I>E. coli-positive routine sample.
(4)
The system fails to test for <I>E. coli when any repeat sample tests positive for total coliform.
(b)
Treatment technique violation.
(1)
A treatment technique violation occurs when a system exceeds a treatment technique trigger specified in § 141.859(a) and then fails to conduct the required assessment or corrective actions within the timeframe specified in § 141.859(b) and (c).
(2)
A treatment technique violation occurs when a seasonal system fails to complete a State-approved start-up procedure prior to serving water to the public.
(c)
Monitoring violations.
(1)
Failure to take every required routine or additional routine sample in a compliance period is a monitoring violation.
(2)
Failure to analyze for <I>E. coli following a total coliform-positive routine sample is a monitoring violation.
(d)
Reporting violations.
(1)
Failure to submit a monitoring report or completed assessment form after a system properly conducts monitoring or assessment in a timely manner is a reporting violation.
(2)
Failure to notify the State following an <I>E. coli-positive sample as required by § 141.858(b)(1) in a timely manner is a reporting violation.
(3)
Failure to submit certification of completion of State-approved start-up procedure by a seasonal system is a reporting violation.
Notes, amendments, and revision history

Source

Source: 78 FR 10354, Feb. 13, 2013, unless otherwise noted.

Authority

Authority: 42 U.S.C. 300f, 300g-1, 300g-2, 300g-3, 300g-4, 300g-5, 300g-6, 300j-4, 300j-9, and 300j-11.

Source

Source: 40 FR 59570, Dec. 24, 1975, unless otherwise noted.