§127.1305. Operations Manual.
33 C.F.R. § 127.1305
Each Operations Manual must contain—
A description of each liquid-transfer system and vapor transfer system, including each mooring area, transfer connection, and (where installed) control room, and a diagram of the piping and electrical systems;
The duties of each person assigned to transfers;
The maximum relief-valve setting or MAWP of the transfer system;
The telephone numbers of supervisors, persons in charge of transfers for the facility, persons on watch in the marine transfer area for LHG, and security personnel of the facility;
A description for each security system provided for the transfer area;
A description of the training programs established under § 127.1302;
The procedures to follow for security violations; and
For each LHG handled, the procedures for transfer that include—
Requirements for each aspect of the transfer (start-up, gauging, cooldown, pumping, venting, and shutdown);
The maximum transfer rate;
The minimum transfer temperature;
Requirements for firefighting equipment; and
Communication procedures.