§127.1109. Lighting systems.
33 C.F.R. § 127.1109
Each waterfront facility handling LHG, at which transfers of LHG take place between sunset and sunrise, must have outdoor lighting that illuminates the marine transfer area for LHG.
All outdoor lighting must be located or shielded so that it cannot be mistaken for any aids to navigation and does not interfere with navigation on the adjacent waterways.
The outdoor lighting must provide a minimum average illumination on a horizontal plane 1 meter (3.3 feet) above the walking surface of the marine transfer area that is—
54 lux (5 foot-candles) at any loading flange; and
11 lux (1 foot-candle) for the remainder of the marine transfer area for LHG.
Notes, amendments, and revision history
Source
Source: CGD 88-049, 60 FR 39796, Aug. 3, 1995, unless otherwise noted.
Authority
Authority: 33 U.S.C. 1504(j)(2); 46 U.S.C. 70011 and 70034; 46 U.S.C. Chapter 701; DHS Delegation No. 00170.1, Revision No. 01.2, paragraph (II)(92)(a).