US Codex
C.F.R.
Browse by date
Notes

§127.1105. Layout and spacing of marine transfer area for LHG.

33 C.F.R. § 127.1105

Each new waterfront facility handling LHG, and all new construction in the marine transfer area for LHG of each facility, must comply with the following:
(a)
Each building, shed, and other structure within each marine transfer area for LHG must be located, constructed, or ventilated to prevent the accumulation of flammable or toxic gases within the structure.
(b)
Each impounding space for flammable LHGs located within the area must be designed and located so that the heat flux from a fire over the impounding space does not cause, to a vessel, damage that could prevent the vessel's movement.
(c)
Each manifold, loading arm, or independent mating flange must be located at least 60 meters (197 feet) from each of the following structures, if that structure is intended primarily for the use of the general public or of railways:
(1)
A bridge crossing a navigable waterway.
(2)
The entrance to, or the superstructure of, a tunnel under a navigable waterway.
(d)
Each manifold, loading arm, or independent mating flange must be located at least 30 meters (98.5 feet) from each public roadway or railway.
Notes, amendments, and revision history

Amendments

[CGD 88-049, 60 FR 39796, Aug. 3, 1995, as amended by USCG-2019-0444, 87 FR 5691, Feb. 2, 2022]

Source

Source: CGD 88-049, 60 FR 39796, Aug. 3, 1995, unless otherwise noted.

Authority

Authority: 33 U.S.C. 1504(j)(2); 46 U.S.C. 70011 and 70034; 46 U.S.C. Chapter 701; DHS Delegation No. 00170.1, Revision No. 01.2, paragraph (II)(92)(a).

Source

Source: CGD 78-038, 53 FR 3376, Feb. 7, 1988, unless otherwise noted.

Amendments

[CGD 88-049, 60 FR 39796, Aug. 3, 1995, as amended by USCG-2019-0444, 87 FR 5691, Feb. 2, 2022]