§127.109. Lighting systems.
33 C.F.R. § 127.109
The marine transfer area for LNG must have a lighting system and separate emergency lighting.
All outdoor lighting must be located or shielded so that it is not confused with any aids to navigation and does not interfere with navigation on the adjacent waterways.
The lighting system must provide an average illumination on a horizontal plane one meter (3.3 feet) above the deck that is—
54 lux (five foot-candles) at any loading flange; and
11 lux (one foot-candle) at each work area.
The emergency lighting must provide lighting for the operation of the—
Emergency shutdown system;
Communications equipment; and
Firefighting equipment.
Notes, amendments, and revision history
Amendments
[CGD 78-038, 53 FR 3376, Feb. 7, 1988, as amended by CGD 88-049, 60 FR 39795, Aug. 3, 1995]
Authority
Authority: 33 U.S.C. 1504(j)(2); 46 U.S.C. 70011 and 70034; 46 U.S.C. Chapter 701; DHS Delegation No. 00170.1, Revision No. 01.2, paragraph (II)(92)(a).
Source
Source: CGD 78-038, 53 FR 3376, Feb. 7, 1988, unless otherwise noted.
Amendments
[CGD 78-038, 53 FR 3376, Feb. 7, 1988, as amended by CGD 88-049, 60 FR 39795, Aug. 3, 1995]