§1910.111. Storage and handling of anhydrous ammonia.
29 C.F.R. § 1910.111
(b) Refrigeration plants where ammonia is used solely as a refrigerant.
(a) Containers shall be stress relieved after fabrication in accordance with the Code, or
(b) Cold-form heads when used, shall be stress relieved, or
(c) Hot-formed heads shall be used.
(a) With a notation “Anhydrous Ammonia.”
(b) With a marking identifying compliance with the rules of the Code under which the container is constructed.
(c) With a notation whether the system is designed for underground or aboveground installation or both.
(d) With the name and address of the supplier of the system or the trade name of the system and with the date of fabrication.
(e) With the water capacity of the container in pounds at 60 °F. or gallons, U.S. Standard.
(f) With the design pressure in pounds per square inch.
(g) With the wall thickness of the shell and heads.
(h) With marking indicating the maximum level to which the container may be filled with liquid anhydrous ammonia at temperatures between 20 °F. and 130 °F. except on containers provided with fixed level indicators, such as fixed length dip tubes, or containers that are filled with weight. Markings shall be in increments of not more than 20 °F.
(i) With the total outside surface area of the container in square feet.
(j) Marking specified on the container shall be on the container itself or on a nameplate permanently attached to it.
(a) Pumps shall be designed for at least 250 p.s.i.g. working pressure.
(b) Positive displacement pumps shall have, installed off the discharged port, a constant differential relief valve discharging into the suction port of the pump through a line of sufficient size to carry the full capacity of the pump at relief valve setting, which setting and installation shall be according to the pump manufacturer's recommendations.
(c) On the discharge side of the pump, before the relief valve line, there shall be installed a pressure gage graduated from 0 to 400 p.s.i.
(d) Plant piping shall contain shutoff valves located as close as practical to pump connections.
(a) Compressors shall be designed for at least 250 p.s.i.g. working pressure.
(b) Plant piping shall contain shutoff valves located as close as practical to compressor connections.
(c) A relief valve large enough to discharge the full capacity of the compressor shall be connected to the discharge before any shutoff valve.
(d) Compressors shall have pressure gages at suction and discharge graduated to at least one and one-half times the maximum pressure that can be developed.
(e) Adequate means, such as drainable liquid trap, shall be provided on the compressor suction to minimize the entry of liquid into the compressor.
(a) Possible refrigeration system upset such as (1) cooling water failure, (2) power failure, (3) instrument air or instrument failure, (4) mechanical failure of any equipment, (5) excessive pumping rates.
(b) Fire exposure determined in accordance with Compressed Gas Association (CGA) S-1, part 3, Safety Relief Device Standards for Compressed Gas Storage Containers, 1959, which is incorporated by reference as specified in § 1910.6, except that “A” shall be the total exposed surface area in square feet up to 25 foot above grade or to the equator of the storage container if it is a sphere, whichever is greater. If the relieving capacity required for fire exposure is greater than that required by (a) of this subdivision, the additional capacity may be provided by weak roof to shell seams in containers operating at essentially atmospheric pressure and having an inherently weak roof-to-shell seam. The weak roof-to-shell seam is not to be considered as providing any of the capacity required in (a) of this subdivision.
(a) Load imposed by heat flow into the container caused by the temperature differential between design ambient temperature and storage temperature.
(b) Load imposed by heat flow into the container caused by maximum sun radiation.
(c) Maximum load imposed by filling the container with ammonia warmer than the design storage temperature.
Notes, amendments, and revision history
Amendments
[39 FR 23502, June 27, 1974, as amended at 43 FR 49748, Oct. 24, 1978; 49 FR 5322, Feb. 10, 1984; 53 FR 12122, Apr. 12, 1988; 61 FR 9238, Mar. 7, 1996; 63 FR 1269, Jan. 8, 1998; 63 FR 33466, June 18, 1998; 72 FR 71069, Dec. 14, 2007]
Authority
Authority: Sections 4, 6, and 8 of the Occupational Safety and Health Act of 1970 (29 U.S.C. 653, 655, 657); Secretary of Labor's Order No. 12-71 (36 FR 8754), 8-76 (41 FR 25059), 9-83 (48 FR 35736), 1-90 (55 FR 9033), 6-96 (62 FR 111), 3-2000 (65 FR 50017), or 5-2007 (72 FR 31159), 4-2010 (75 FR 55355) or 1-2012 (77 FR 3912), as applicable; and 29 CFR part 1911. Sections 1910.103, 1910.106 through 1910.111, and 1910.119, 1910.120, and 1910.122 through 1910.126 also issued under 29 CFR part 1911. Section 1910.119 also issued under Section 304, Clean Air Act Amendments of 1990 (Pub. L. 101-549), reprinted at 29 U.S.C.A. 655 Note. Section 1910.120 also issued under Section 126, Superfund Amendments and Reauthorization Act of 1986 as amended (29 U.S.C.A. 655 Note), and 5 U.S.C. 553.
Authority
Authority: 33 U.S.C. 941; 29 U.S.C. 653, 655, 657; Secretary of Labor's Order No. 12-71 (36 FR 8754); 8-76 (41 FR 25059), 9-83 (48 FR 35736), 1-90 (55 FR 9033), 6-96 (62 FR 111), 3-2000 (65 FR 50017), 5-2002 (67 FR 65008), 5-2007 (72 FR 31160), 4-2010 (75 FR 55355), 1-2012 (77 FR 3912), 08-2020 (85 FR 58393), or 07-2025 (90 FR 27878); 29 CFR part 1911; and 5 U.S.C. 553, as applicable.
Source
Source: 39 FR 23502, June 27, 1974, unless otherwise noted.